Model No.︰QPM2102D
Brand Name︰siemens(LANDIS)
Country of Origin︰Germany
Unit Price︰-
Minimum Order︰1 pc
• With maintenance-free CO2 sensing element based on optical infrared absorption
measurement (NDIR1)
• and – depending on the type of sensor – VOC2) sensing element, based on a
heated tin dioxide semiconductor
• CO2 temperature and CO2 humidity-temperature multisensor
• No recalibrations required
• Operating voltage AC 24 V or DC 15…35 V
• Signal outputs DC 0...10 V
In air ducts of ventilation and air conditioning plant to enhance room comfort and to
optimize energy consumption by providing demand-controlled ventilation. The sensor
acquires:
• CO2 concentrations
• VOC concentrations as an indication of odors in the duct air, such as tobacco smoke,
body odor, or material fumes
• The relative humidity of the duct air
• The duct air temperature
The QPM21… can be used as a:
• Control sensor in the supply or extract air duct
• Transmitter for building automation and control systems and / or display units
Typical use:
• Acquisition of CO2 and VOC concentrations:
In party rooms, lounges, fair pavillions and exhibition halls, restaurants, canteens,
shopping malls, sports gymnasiums, sales rooms, and conference rooms
• Acquisition of CO2 concentrations:
In ventilation plant of rooms with varying occupancy levels where smoking is prohibited, such as museums, theatres, movie theatres, auditoriums, office spaces and
school rooms
• The QPM21… sensors are not suited for use as safety devices, such as gas or
smoke warning devices!
• The sensors must not be used outdoors!
Type reference | CO2 measuring range | VOC sensitivity | Temperature measuring range | Humidity measuring range | Measured value display |
QPM2100 | 0…2000 ppm | --- | --- | --- | no |
QPM2102 | 0…2000 ppm | low (R1) Normal (R2) High(R3) | --- | --- | no |
QPM2102D | 0…2000 ppm | low (R1) Normal (R2) High(R3) | --- | --- | yes |
QPM2160 | 0…2000 ppm | --- | 0...50 °C / −35...+35 °C | --- | no |
QPM2160D | 0…2000 ppm | --- | 0...50 °C / −35...+35 °C | --- | yes |
QPM2162 | 0…2000 ppm | --- | 0...50 °C / −35...+35 °C | 0---100% | no |
QPM2162D | 0…2000 ppm | --- | 0...50 °C / −35...+35 °C | 0---100% | yes |
Export Markets︰ BUILDING CONTROL, HVAC
Min Order︰ 1
Ship Date︰ 3 DAYS