ITEM |
TYPE NO. |
operated VOLTAGE |
Type of control
(Control signal) |
Run-time (s) |
Springreturn
function |
Springreturn
time
[s] |
1 |
SQS35.00 |
230VAC |
3-position |
150 |
no |
--- |
2 |
SQS35.03 |
230VAC |
3-position |
35 |
no |
--- |
3 |
SQS35.50 |
230VAC |
3-position |
150 |
yes |
8 |
4 |
SQS35.53 |
230VAC |
3-position |
35 |
yes |
8 |
5 |
SQS65 |
24VAC |
DC 0...10 V |
35 |
no |
--- |
6 |
SQS65.2 |
24VAC |
DC 0...10 V |
35 |
no |
--- |
7 |
SQS65.5 |
24VAC |
DC 2...10 V |
35 |
no |
--- |
8 |
SQS85.00 |
24VAC |
3-position |
150 |
no |
--- |
9 |
SQS85.03 |
24VAC |
3-position |
35 |
no |
--- |
|
|
|
|
Specifications︰ | Electric actuators • SQS35... AC 230 V operating voltage, 3-position control signal • SQS85...AC 24 V operating voltage, 3-position control signal • SQS65... AC 24 V operating voltage, DC 0 ...10 V or DC 2 ... 10 V control signal • Positioning force 400 N • Stroke 5.5 mm • For direct mounting on valves, without adjustment • Optional auxiliary switch for additional functions with SQS35.00, SQS35.03, SQS85.00 and SQS85.03 • Choice of actuators with or without spring return function to DIN 32 730 • Non-spring return actuators with position indication and with manual adjustment • Spring return actuators with position indication and without manual adjustment Used to operate 2-port and 3-port valves with a 5.5 mmstroke. For valve types VVG44..., VVG55..., VVP45..., VMP43..., VMP44..., VMP45..., VXG44..., VXP45..., VVI52... • Area of application in accordance with IEC 721-3-3 Class 3K5 • Ambient temperatures:−5 ... +50 °C • Temperature of medium in the connected valve:+2 ...+130 °C • The use of mounting kit ASK30 enables the following valves with a 4mm or 5.5 mm stroke to be operated: X3i..., VVG45..., VXG45..., VXG46... and VVI51... The reversible synchronous motor is driven with a 3-position control signal (SQS35… and SQS85…) or a proportional DC 0…10 V (SQS65, SQS65.5) or DC 2...10 V (SQS65.2) control signal. The corresponding stroke is generated via an anti-locking gear mechanism. 3-position control at terminals Y1 or Y2: • Voltage at Y1: Valve stem retracts, through-port opens • Voltage at Y2: Valve stem extends, through-port closes • No voltage at Y1 or Y2: Valve stem holds current position |
Advantages︰ | Connector S1 (under the cover, on the printed circuit board) can be repositioned to change the flow characteristic of valves with a 5.5 mm stroke from “equal percentage” to “linear”; in all cases the flow characteristic relates to the through-port of the valve. • Connecting S1 to pins A and C produces an equal percentage flow characteristic (factory setting), primarily for heating applications • Connecting S1 to pins B and C produces a linear flow characteristic, primarily for cooling applications • For automatic operation, S1 must be connected either to pins A and C, or B and C, depending on the required flow characteristic. |
Export Markets︰ | building automation,hvac |
Min Order︰ | 1 |
Ship Date︰ | 3 DAYS |
|
|
Product Image
|